Emergency Procedures.

Emergency Procedures.

*Low Water:- Make sure pumps are running and valves are open
Start pumps and open valves if necessary.
*High Water:- Blow down Boiler to correct level.
*Live coals falling off rear of stoker;- Adjust stoker speed with fuel trim knob.
*Safety valves lifting:- Stop Fans, check blow down valve is closed and make
sure pumps are running.
*Pump tripping out:- Change over to second pump and call electrician.
*Stoker Jamming,Shear pin breaking:- Replace shear pin - Call out fitter - if necessary push fire off grate.
*I D Fan Tripping:- Stop F D fans, Close dampers and call electrician, close
crown valve and bank or remove fires from boiler if necessary.
*Alarm Sounding , Extra Low Water:- Close crown valve,check that feed pump is running, if necessary change over to stand-by pump. Remove fires from boiler if water does not fill boiler. *Power Failure:- Close crown valve, remove shear pin from stoker drive fit crank handle and remove fires from stoker, de-ash boiler.